An industrial generator is a diesel generator set with 3 phases 380/220V output, rated from tens to thousands of kVA, used as standby or prime power for factories, buildings, hospitals and construction sites. Unlike home generators, industrial sets are designed to run for many hours, handle large motor loads and have automatic controllers.
247Power (Thien Quang Company) supplies brand-new generators with full CO/CQ documents, with Cummins, Perkins, Doosan, FPT, Volvo, Baudouin and Cooper engines. Our engineers survey your site, size the generator to your real load, handle the complete installation and provide regular maintenance afterwards.
Prime power is what the generator can deliver continuously; standby power is about 10% higher and is only for grid outages. Choose a generator whose normal load is about 70 – 80% of its prime rating.
kW = kVA × power factor (usually 0.8), so a 100 kVA generator gives about 80 kW. When adding up loads, convert everything to the same unit so you don't undersize.
Direct-on-line pumps, compressors and lifts can draw 3 – 7 times their rated current when starting. Allow extra capacity or use soft starters or VFDs.
A soundproof canopy cuts noise near homes and offices. An ATS panel switches to the generator when the grid fails and back when power returns.
| Use | Suggested power |
|---|---|
| Shops, small offices | 20 – 60 kVA |
| Office buildings, hotels, schools | 100 – 500 kVA |
| Workshops, industrial parks | 250 – 1,500 kVA |
| Hospitals, data centers, large factories | 500 – 3,750 kVA (one set or several synchronized sets) |
These figures are only a guide. The actual rating depends on your equipment list and starting currents – 247Power can survey and calculate it for you.
The table shows current website prices for the Cummins India 82.5 – 400 kVA range. Other brands are quoted by configuration, because the price also depends on the alternator, soundproof canopy, ATS panel and installation conditions.
| Model | Power | Voltage | Price |
|---|---|---|---|
| CUMMINS INDIA 82.5 kVA | 82.5 kVA | 380/220V – 3 phases – 4 wire – 4 pole | 320,000,000 VND |
| CUMMINS INDIA 100 kVA | 100kVA | 380/220V – 3 phases – 4 wire – 4 pole | 370,000,000 VND |
| CUMMINS INDIA 125 kVA | 125kVA | 380/220V – 3 phases – 4 wire – 4 pole | 390,000,000 VND |
| CUMMINS INDIA 160 kVA | 160kVA | 380/220V – 3 phases – 4 wire – 4 pole | 520,000,000 VND |
| CUMMINS INDIA 200 kVA | 200kVA | 380/220V – 3 phases – 4 wire – 4 pole | 620,000,000 VND |
| CUMMINS INDIA 250 kVA | 250kVA | 380/220V – 3 phases – 4 wire – 4 pole | 770,000,000 VND |
| CUMMINS INDIA 300 kVA | 300kVA | 380/220V – 3 phases – 4 wire – 4 pole | 920,000,000 VND |
| CUMMINS INDIA 400 kVA | 400kVA | 380/220V – 3 phases – 4 wire – 4 pole | 1,160,000,000 VND |
Prices may change over time and with configuration. Call 247Power for the latest quote.
If the plant has a stable grid and the set only runs during outages, a standby rating (ESP) is usual, for up to 200 hours a year. If the set is the main power source or runs for long hours, choose a prime rating (PRP). Both ratings require the average load over 24 hours to stay within 70%. On 247Power spec sheets, “continuous power” means prime power. Read more Prime and standby power explained.
Enough maintenance space, enough air for the engine and a path for hot air to escape.
Carries exhaust gas to a safe area and reduces noise for the surroundings.
Size it from the fuel consumption and the hours the set must run without refuelling.
Switches the source automatically in an outage, with protection matched to the load.
247Power can survey the site and deliver the full job through its generator consulting, design and installation service.
Read more: diesel generators, petrol generators, 3 phases Generator and how to buy a low-cost generator.
Add up the power of everything that must run during an outage, allow for the starting current of large motors, then choose a generator whose normal load is about 70 – 80% of its prime rating. 247Power surveys your site and sends a sizing calculation before quoting.
Almost all industrial generators run on diesel: it is durable, economical at high loads and safer than petrol. Consumption depends on the load; the fuel tank is sized for the hours of continuous running you need.
Yes – brand new, with CO/CQ and the manufacturer's warranty. 247Power installs, load-tests and trains your operators at handover.
Yes. 247Power rents generators by the day, week or month for events, construction sites or while your own generator is being repaired, including transport and an on-site technician.
Send us your equipment list or call a 247Power engineer – we survey, size and quote.