| GENERAL SPECIFICATIONS |
| Manufacturer |
Cummins India |
| Model |
C160D5P |
| Genset origin |
India |
| Prime power |
160kVA |
| Maximum power |
176kVA |
| Voltage – phases – wires – poles |
380/220V – 3 phases – 4 wire – 4 pole |
| Optional voltage range |
380-400V / 220-230V |
| Frequency – speed |
50Hz – 1500 v/ph |
| Power factor (cos phi) |
0,8 |
| Current (A) |
223 |
| Dimensions (L × W × H) (mm) |
4000 x 1150 x 1850 (soundproof) |
| Dry weight |
2603 kg |
| Fuel tank capacity |
290 L |
| Noise at 1 m, 75% load |
75 dB at 1 m |
| Condition |
Brand new |
| ENGINE |
| Brand |
Cummins® |
| Model |
QSB5.9-G2 |
| Origin |
Cummins India |
| Engine type |
4-stroke diesel engine |
| power engine (bhp) |
206 |
| Gross engine output (bhp) |
197 |
| Cooling system |
Water-cooled with radiator fan |
| Aspiration |
Turbocharged and Charge Air cooled
(Turbocharged, aftercooled) |
| Cylinders – arrangement |
6 cylinders – in-line |
| Bore × stroke (mm) |
102 x 120 |
| Compression ratio |
16,5:1 |
| Displacement (L) |
5,88 |
| Fuel |
Diesel (DO) |
| Fuel consumption at 75% load (L/h) |
29,93 |
| Fuel consumption at 100% load (L/h) |
35,95 |
| Manufacturing standard |
ISO 8528-5 G2 |
| Starting system |
12 V DC electric |
| Lube oil specification |
CI4+ 15W40 |
| Working lube oil capacity (L) |
12,3 – 14,2 |
| Total lube oil capacity (L) |
15,7 |
| Total coolant capacity (L) |
25,6 |
| Exhaust outlet size (inch) |
4 |
| Weight (engine + radiator) (kg) |
552 |
| Engine dimensions (L×W×H) (mm) |
1066 x 642 x 1029 |
| Mean piston speed (m/s) |
6 |
| Exhaust temperature (°C) |
522 |
| ALTERNATOR |
| Brand |
Stamford |
| Model |
UCI274F |
| Origin |
Cummins India |
| Alternator type |
AC, 3 phases, 4 pole, rotating field, brushless
single bearing, self-excited (PMG) |
| Voltage – phases – wires |
220/380V – 3 phases – 4 wire |
| Protection class |
IP23 |
| Insulation class |
H / H |
| Voltage regulation |
±1% |
| CONTROLLER |
| Brand |
Cummins® |
| Model |
PowerCommand® 1.1 |
| Main specifications and functions |
– Easy-to-use LCD and LED indicators
– Emergency stop button
– Remote start
– Shows all generator and engine operating parameters
– Protection, alarms and shutdown when operating conditions are out of range
– Operating data logging
– And much more… |
| STANDARD EQUIPMENT |
| Soundproof canopy |
– Specially designed to meet the strict MoEF / CPCB limit of 75 dBA @ 1 m at 75% load
– Canopy made of steel sheet over 2 mm thick, chemically treated against rust and corrosion, gloss blue finish
– Tank pre-treatment and UV-resistant powder coating on all parts to withstand harsh environments
– High-quality noise-insulating, fire-resistant lining; P.U. foam insulation compliant with ISO 8183
– The canopy has two separate compartments (engine room and heat exhaust) with ventilation grilles for better airflow. Inspection, refuelling and coolant points are conveniently placed.
– Air inlets specially designed for stable operation at rated load |
| Frame and base |
– Load-bearing frame of V or U steel sections at least 3 mm thick, electrically welded for strength, with anti-vibration mounts for smooth, balanced running
– Engine and alternator mounted on a base frame with rubber anti-vibration mounts for smooth, balanced running |
| Fuel tank |
– 290 L tank built into the base frame, for over 8 hours of continuous running |
| Silencer |
– Designed and built for minimum noise |