Generators for homes and shops
A home generator (also called a residential generator) is a small set, usually 3 to 30 kVA, used in houses, villas, shops, restaurants and small clinics during outages. Petrol sets are compact, low-priced and suit short runs. Diesel sets last longer and use less fuel when they must run for many hours.
247Power distributes Honda, Huu Toan (Honda and Kohler engines, assembled in Vietnam), Kubota and Yanmar (Japan) generators, in 1 phase 220V and 3 phases 380V, open or soundproof.
Things to keep in mind
Work out your load
List what must run during an outage: lights, fans, fridge, pump, air conditioners… Air conditioners and pumps need 2 – 3 times their rated power to start, so choose a generator with 20 – 30% spare capacity.
1 phase or 3 phases
Homes usually use 1 phase 220V. If you have a lift, a large pump or a 3 phases grid supply, choose a 3 phases generator to balance the load.
Noise level
In residential areas, choose a soundproof or low-speed diesel generator and place it away from bedrooms and neighbours.
Safe installation
Place the generator in a well-ventilated spot, never indoors – the exhaust contains CO. Connect it through a changeover switch or ATS so it never feeds back into the grid.
Suggested power ratings
| Use | Suggested power |
|---|---|
| Lights, fans, TV, fridge, wifi | 3 – 5 kVA |
| Townhouse with 1 – 2 air conditioners and a water pump | 6 – 10 kVA |
| Villa with several air conditioners and a home lift | 12 – 20 kVA (usually 3 phases) |
| Shops, restaurants, small clinics | 10 – 30 kVA |
These figures are only a guide. The actual rating depends on your equipment list and starting currents – 247Power can survey and calculate it for you.
Home generator price list
The models below run on petrol and supply 220 V 1 phase power, suiting homes and small shops. Prices come directly from the products listed on this website.
| Model | Power | Voltage | Price |
|---|---|---|---|
| FA3000P 2.3 kVA | 2.3kVA / 2.3kW | 220V – 1 phase | 11,000,000 VND |
| HK4500 3 kVA | 3kVA / 3kW | 220V – 1 phase | 11,500,000 VND |
| HK7500 5.6 kVA | 5.6 kVA / 5.6 kW | 220V – 1 phase | 21,000,000 VND |
| FA6500X 5 kVA | 5 kVA / 5 kW | 220V – 1 phase | 28,000,000 VND |
| EZ6500CXS 5 kVA | 5 kVA / 5 kW | 220V – 1 phase | 29,000,000 VND |
| HK16000SDX MT 10 kVA | 10 kVA / 10 kW | 220V – 1 phase – 2 wire | 73,000,000 VND |
| HK16000SDX GT 10 kVA | 10 kVA / 10 kW | 220V – 1 phase – 2 wire | 87,000,000 VND |
Prices may change over time. Call 247Power for the latest quote.
How to calculate home generator power
Add up the power of the appliances you need, add the starting power of the largest one, then leave a 20 – 30% margin. The assumed example below shows the method. For a real calculation, use the figures on each appliance label:
| Step | Power |
|---|---|
| Lights and fans | 300 W |
| TV | 100 W |
| Fridge | 150 W |
| Air conditioner | 1,000 W |
| Water pump | 750 W |
| Total running load | 2,300 W |
| Add air conditioner starting power (3 times, so 2,000 W more) | 4,300 W |
| 30% margin | About 5,600 W |
For this example, choose a set of about 6 kVA or more. Read more How to calculate generator power.
Petrol or diesel for a home generator?
Comparing two models on sale shows the main difference: the diesel set delivers more power at similar fuel use, but is much heavier.
| Criteria | HK7500 (petrol) | Kubota TK8SL (diesel) |
|---|---|---|
| Power | 5.6 kVA rated | 8 kVA continuous |
| Voltage | 220 V, 1 phase | 220 V, 1 phase |
| Fuel consumption | 3 L/h | 3.1 litres per hour at full load |
| Dry weight | 77 kg | 485 kg |
A petrol set suits infrequent outages and a need for something compact. A diesel set suits long running hours. If your load is larger than a typical home, see Industrial Generators.
How to choose a generator
Read more: diesel generators, petrol generators, 3 phases Generator and how to buy a low-cost generator.
Suitable models
Related services
Frequently asked questions
What size generator does a home need?
For lights, fans and a fridge, 3 – 5 kVA is enough. To also run air conditioners and a pump, choose 6 – 10 kVA. Send 247Power your equipment list for an exact calculation.
Petrol or diesel – which is better?
Petrol generators are small, light and cheap – good for rare, short outages. Diesel generators are more durable, use less fuel and suit long running hours or ratings from about 10 kVA up.
Can it start automatically during an outage?
Yes, with an electric-start generator and an ATS panel: when the power fails the generator starts and takes over; when power returns it switches back to the grid and shuts down.
How often does a generator need servicing?
Change the oil after the first 50 hours, then every 100 – 200 hours or 6 months depending on the brand; even if rarely used, run it for 10 – 15 minutes every month.
Send us your equipment list or call a 247Power engineer – we survey, size and quote.